Machine Recycling Discussion and Moderated Newsgroup   >   Full Machines   >   Tekmar 265 boiler control three modulating boiler & dhw

Tekmar 265 boiler control three modulating boiler & dhw


Indoor Only: 32 -104 F < 90% RH non-condensing
230 V (ac) 5 A-1/3 hp- pilot duty 240 VA
Control Description The Boiler Control 265 is a microprocessor-based control designed to operate up to three modulating boilers. The 265 can provide either outdoor reset and setpoint operation or outdoor reset and DHW operation. The 265 provides either sequential or parallel modulation and has Equal Run Time Rotation of the boilers. The control also operates the system pump and individual boiler pumps. The 265 provides either a 0 -20 mA or 4 -20 mA signal to each boiler. A contact is also available for either a combustion air damper or external alarm. The control can provide outdoor reset using an outdoor sensor or the control can accept a 0 -10 V (dc) signal from an EMS / BAS to establish the required water temperature.
Microprocessor PID control; This is not a safety (limit) control
3.5 lb. (1600 g), Enclosure A, blue modified PVC plastic
6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm)
CSA C US, meets ICES & FCC regulations for EMI/RFI
Indoor use only, 32 to 104 F (0 to 40 C), < 90% RH non-condensing
115 V (ac) 10% 50/60 Hz 600 VA
230 V (ac) 5 A, 1/3 hp, pilot duty 230 VA
0-20 mA / 4-20 mA (up to 1000 load)
NTC thermistor, 10 k @ 77 F (25 C 0.2 C) +=3892
Outdoor Sensor 070 and 2 of Universal Sensor 071



Tekmar 265 boiler control three modulating boiler & dhw